- Part No: M1MN30T3L
- Product Type: NOARK® Motor-Circuit Protector
- Brand: NOARK®
- Series: M1M
- Frame Size: Frame M1
- IC Class: N (High Interrupting Capacity)
- Interrupting Capacity: 65kA @ 480Vac
- Rated Current (Amps): 30A
- No. Of Poles: 3
- Connection Type: Lug Line/Load Side
- Cam Setting: A, B, C, D, E, F, G
- Full Load Current at Cam Setting A: 11.5 to 13.7 A
- Full Load Current at Cam Setting B: 13.8 to 16 A
- Full Load Current at Cam Setting C: 16.1 to 18.3 A
- Full Load Current at Cam Setting D: 18.4 to 20.6 A
- Full Load Current at Cam Setting E: 20.7 to 22.9 A
- Full Load Current at Cam Setting F: 23 to 25.2 A
- Full Load Current at Cam Setting G: 25.3 to 26.1 A
- (MCP) Trip Setting at Cam Setting A: 150
- (MCP) Trip Setting at Cam Setting B: 180
- (MCP) Trip Setting at Cam Setting C: 210
- (MCP) Trip Setting at Cam Setting D: 240
- (MCP) Trip Setting at Cam Setting E: 270
- (MCP) Trip Setting at Cam Setting F: 300
- (MCP) Trip Setting at Cam Setting G: 330
For any information about products, please contact us.
*Photos for reference purposes only.
Original: $214.58
-65%$214.58
$75.10

Description
Product Details : NOARK® Motor-Circuit Protector 30A Frame M1, N IC Class 3P | M1MN30T3L
- Part No: M1MN30T3L
- Product Type: NOARK® Motor-Circuit Protector
- Brand: NOARK®
- Series: M1M
- Frame Size: Frame M1
- IC Class: N (High Interrupting Capacity)
- Interrupting Capacity: 65kA @ 480Vac
- Rated Current (Amps): 30A
- No. Of Poles: 3
- Connection Type: Lug Line/Load Side
- Cam Setting: A, B, C, D, E, F, G
- Full Load Current at Cam Setting A: 11.5 to 13.7 A
- Full Load Current at Cam Setting B: 13.8 to 16 A
- Full Load Current at Cam Setting C: 16.1 to 18.3 A
- Full Load Current at Cam Setting D: 18.4 to 20.6 A
- Full Load Current at Cam Setting E: 20.7 to 22.9 A
- Full Load Current at Cam Setting F: 23 to 25.2 A
- Full Load Current at Cam Setting G: 25.3 to 26.1 A
- (MCP) Trip Setting at Cam Setting A: 150
- (MCP) Trip Setting at Cam Setting B: 180
- (MCP) Trip Setting at Cam Setting C: 210
- (MCP) Trip Setting at Cam Setting D: 240
- (MCP) Trip Setting at Cam Setting E: 270
- (MCP) Trip Setting at Cam Setting F: 300
- (MCP) Trip Setting at Cam Setting G: 330